other phenomena, for example wind, a greater number of auto reclosing attempts
(shots) can be motivated.
t1 1Ph, t1 2Ph, t1 3Ph
: There are separate settings for the first shot for single-, two-
and three-phase auto reclosing dead times.
Single-phase auto reclosing dead time: A typical setting is
t1 1Ph
= 800ms. Due to
the influence of energized phases the arc extinction may not be instantaneous. In
long lines with high voltage the use of shunt reactors in the form of a star with a
neutral reactor improves the arc extinction.
Three-phase auto reclosing dead time: Different local phenomena, such as
moisture, salt, pollution, can influence the required dead time. Some users apply
Delayed Auto Reclosing (DAR) with delays of 10s or more.
Extended t1
: The time extension below is controlled by the
Extended t1
setting.
tExtended t1
: A time extension delay,
tExtended t1
, can be added to the dead time
delay for the first shot. It is intended to come into use if the communication
channel for permissive line protection is lost. The communication link in a
permissive (not strict) line protection scheme, for instance a power line carrier
(PLC) link, may not always be available. If lost, it can result in delayed tripping at
one end of a line. There is a possibility to extend the auto reclosing dead time in
such a case by use of the
PLCLOST
input, and the
tExtended t1
setting. Typical
setting in such a case:
Extended t1
=
On
and
tExtended t1
= 0.8 s.
t1 3PhHS
: There is also a separate time setting facility for three-phase high-speed
auto reclosing,
t1 3PhHS
. This high-speed auto reclosing is activated by the
STARTHS
input and is used when auto reclosing is done without the requirement of
synchrocheck conditions to be fulfilled. A typical dead time is 400ms.
t2 3Ph
,
t3 3Ph
,
t4 3Ph
,
t5 3Ph
: The delay of auto reclosing shot two and possible
later shots are usually set at 30s or more. A check that the circuit breaker duty
cycle can manage the selected setting must be done. The setting can in some cases
be restricted by national regulations. For multiple shots the setting of shots two to
five must be longer than the circuit breaker duty cycle time.
MasterSlave settings
Priority
: In single circuit breaker applications, one sets
Priority
= None. At
sequential reclosing the auto recloser for the first circuit breaker, e.g. near the
busbar, is set as master (High) and the auto recloser for the second circuit breaker
is set as slave (Low).
tWaitForMaster
: The slave should take the duration of the circuit breaker closing
time of the master into consideration before sending the circuit breaker closing
command. A setting
tWaitForMaster
sets a maximum wait time for the
WAIT
input
to reset. If the wait time expires, the auto reclosing cycle of the slave is inhibited.
The maximum wait time,
tWaitForMaster
for the second circuit breaker is set
longer than the auto reclosing dead time plus a margin for synchrocheck conditions
to be fulfilled for the first circuit breaker. Typical setting is 2sec.
Section 15
1MRK 506 369-UEN B
Control
638
Line distance protection REL670 2.2 IEC
Application manual
Содержание REL670 2.2 IEC
Страница 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 32: ...26 ...
Страница 70: ...64 ...
Страница 110: ...104 ...
Страница 152: ...146 ...
Страница 564: ...558 ...
Страница 570: ...564 ...
Страница 592: ...586 ...
Страница 706: ...700 ...
Страница 804: ...798 ...
Страница 848: ...842 ...
Страница 860: ...854 ...
Страница 882: ...876 ...
Страница 896: ...890 ...
Страница 906: ...900 ...
Страница 907: ...901 ...