Operate
Angle1(2)
Power1(2)
P
Q
en06000441.vsd
IEC06000441 V1 EN-US
Figure 281:
Underpower mode
The setting
Power1(2)
gives the power component pick up value in the
Angle1(2)
direction. The setting is given in p.u. of the generator rated power, see
equation
Minimum recommended setting is 0.2% of S
N
when metering class CT inputs into
the IED are used.
3
N
S
UBase IBase
=
×
×
EQUATION1708 V1 EN-US
(Equation 494)
The setting
Angle1(2)
gives the characteristic angle giving maximum sensitivity of
the power protection function. The setting is given in degrees. For active power the
set angle should be 0° or 180°. 0° should be used for generator low forward active
power protection.
Section 9
1MRK 506 369-UEN B
Current protection
518
Line distance protection REL670 2.2 IEC
Application manual