IEC06000592-2-en.vsd
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
1
1.5
2
2.5
3
3.5
Degree of series compensation [%]
In
c
re
a
se
i
n
p
o
we
r
tr
a
n
s
fe
r
Power transfer with constant angle difference
Degree of
compensation
Multiple of power over
a non-compensated line
IEC06000592 V2 EN-US
Figure 198:
Increase in power transfer over a transmission line depending on
degree of series compensation
8.13.3.3
Voltage and current inversion
GUID-CB215C0F-F4FA-4646-9235-AE6DB0255E80 v1
Series capacitors influence the magnitude and the direction of fault currents in
series compensated networks. They consequently influence phase angles of
voltages measured in different points of series compensated networks and this
performances of different protection functions, which have their operation based on
properties of measured voltage and current phasors.
Voltage inversion
GUID-E649A7CB-9877-48F7-8AB3-25D5E8695673 v1
presents a part of series compensated line with reactance X
L1
between
the IED point and the fault in point F of series compensated line. The voltage
measurement is supposed to be on the bus side, so that series capacitor appears
between the IED point and fault on the protected line. Figure
corresponding phasor diagrams for the cases with bypassed and fully inserted
series capacitor.
Voltage distribution on faulty lossless serial compensated line from fault point F to
the bus is linearly dependent on distance from the bus, if there is no capacitor
included in scheme (as shown in figure
). Voltage U
M
measured at the bus is
equal to voltage drop
D
U
L
on the faulty line and lags the current I
F
by 90 electrical
degrees.
The situation changes with series capacitor included in circuit between the IED
point and the fault position. The fault current I
F
(see figure
the series capacitor, generally decreases total impedance between the sources and
the fault. The reactive voltage drop
D
U
L
on X
L1
line impedance leads the current
by 90 degrees. Voltage drop
D
U
C
on series capacitor lags the fault current by 90
degrees. Note that line impedance X
L1
could be divided into two parts: one
between the IED point and the capacitor and one between the capacitor and the
fault position. The resulting voltage U
M
in IED point is this way proportional to
sum of voltage drops on partial impedances between the IED point and the fault
position F, as presented by
Section 8
1MRK 506 369-UEN B
Impedance protection
376
Line distance protection REL670 2.2 IEC
Application manual
Содержание REL670 2.2 IEC
Страница 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 32: ...26 ...
Страница 70: ...64 ...
Страница 110: ...104 ...
Страница 152: ...146 ...
Страница 564: ...558 ...
Страница 570: ...564 ...
Страница 592: ...586 ...
Страница 706: ...700 ...
Страница 804: ...798 ...
Страница 848: ...842 ...
Страница 860: ...854 ...
Страница 882: ...876 ...
Страница 896: ...890 ...
Страница 906: ...900 ...
Страница 907: ...901 ...