System run – Cooling mode
The chiller is running with Heat Pump Duty enabled and the Heat Pump Duty Operational mode
setpoint set to Cooling mode. In this mode, the Heat Pump is controlling the Leaving Chilled Liquid
Temperature to the Leaving Chilled Liquid Temperature Setpoint.
System coastdown
The chiller has shut down and the Post-run lubrication is being performed. The Coastdown
duration is determined by the setting of the Coastdown (standard or enhanced) and Coastdown
Time Setpoints. If the Coastdown setpoint is set to enhanced (steam turbine applications), it
is 15 minutes. If set to standard (electric motor applications), it is programmable over a range
determined by the Chiller Style/Compressor Setpoint (for style G/K6-K7, the range is 240 (default) to
900 seconds.
Start inhibit
The chiller is prevented from being started due to the reason displayed on the Details Line of the
Status Bar.
Vanes closing before shutdown
Displayed while the Pre-Rotation Vanes are closing during a Soft Shutdown. During Soft Shutdowns,
the Vanes are driven fully closed prior to shutting down the compressor. When the Vane Motor End
Switch closes, indicating the Vanes have fully closed (or 3.5 minutes have elapsed, whichever occurs
first), the Run Signal is removed from the compressor motor starter and a System Coastdown is
performed. Soft Shutdowns are initiated by the following:
1. Leaving Chilled Liquid – Low temperature
2. Remote Stop
3. Multi-Unit Cycling – Contacts Open
4. System Cycling – Contacts Open
5. Control Panel – Schedule
6. Operator Initiated at Keypad
While the Vanes are closing during any Soft Shutdown, if a Local Stop is initiated with the
Compressor Switch or any faults other than those listed above occur, the Soft Shutdown is
terminated and it will immediately perform a System Coastdown.
Run messages
Leaving chilled liquid control
The chiller is running, controlling the Leaving Chilled Liquid to the Leaving Chilled Liquid
Temperature Setpoint. There are no system conditions inhibiting this operation.
Heat pump – Leaving chilled liquid control
The Heat Pump is running, controlling the Leaving Chilled Liquid Temperature to the Leaving
Chilled Liquid Temperature Setpoint. In this mode, Heat Pump Duty is enabled and the Heat Pump
Duty Operational mode setpoint is set to Cooling mode.
Current pulldown limit
The Pulldown Demand Limit Setpoint timer is in effect and the Compressor Motor current is
greater than or equal to the Pulldown Demand Current Limit Setpoint value. The Pre-Rotation Vane
operation is being inhibited as described in Motor – High Current Limit message below.
YK-EP Style B Centrifugal Chiller
190
Summary of Contents for 160.87-OM1
Page 2: ...2 YK EP Style B Centrifugal Chiller ...
Page 6: ...6 YK EP Style B Centrifugal Chiller ...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller ...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228 ...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller ...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230 ...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller ...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232 ...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller ...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234 ...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller ...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236 ...