RS-232 pin assignments (DB9 PC signal set)
(Most laptops)
Pin 1
Received line Signal Detector
(Data Carrier Detect)
Pin 2
Recieved Data
Pin 3
Transmit Data
Pin 4
Data Terminal Ready
Pin 5
Signal Ground
Pin 6
Data Set Ready
Pin 7
Request To Send
Pin 8
Clear To Send
Pin 9
Ring Indicator
The connector on the PC has male pins; therefore, the mating cable needs to terminate DB9/F
(female pin) connector.
Brecknell – Brecknell CP130
•
Dimensions: 5.25″ Long x 3.75″ Wide x 2.5″ High
•
Paper: Thermal 57mm (2.25”)
•
Type: Dot Matrix
•
Purchase: 800-637-0529 (North America) +44 (0) 845-246-6717 (Europe and ME)
•
P/N AWT 05-505788 (printer, cable, 1 roll of paper)
•
P/N AWT 05-505594 (power supply)
•
P/N AWT 05-505671 (case, 20 rolls of paper)
Printer connections
Connect the printer to the Control Center Microboard as follows. Only one printer can be connected
at a time.
Table 208: Brecknell CP130
Modify the cable and connect as shown below
Microboard
Printer
Function
J2-4
Pin 3
TX Data to the printer
J2-2
Pin 5
Busy signal from the printer
J2-9
Pin 6
Signal Common
225
YK-EP Style B Centrifugal Chiller
Summary of Contents for 160.87-OM1
Page 2: ...2 YK EP Style B Centrifugal Chiller ...
Page 6: ...6 YK EP Style B Centrifugal Chiller ...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller ...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228 ...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller ...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230 ...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller ...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232 ...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller ...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234 ...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller ...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236 ...