Table 117: Programmable
Button
Description
ACC Mapping Enable
Sets the Delta T (Leaving Chilled Liquid Temperature - Setpoint)
needed to be met to enable surge mapping and speed reduction
initially on startup. Programmable over the range of 0.5°F to 20.0°F
(default 1.0°F).
Surge Margin Adjust
This value determines how close the frequency reduction will be
allowed to get to the surge line. Programmable over the range of
0.0 (default) to 25.0 Hz. Service Technicians should refer to
Variable
Speed Drive – Service Instructions (Form 160.00-M4)
prior to adjusting
this setpoint.
Surge Sensitivity
Allows the Service Technician to adjust the sensitivity of the ACC
Surge Detection in the Microboard (surges that occur while the drive
is running at less than maximum frequency). Programmable over
the range of 1.5 to 2.5 with default of 2.0. Smaller values increase
the sensitivity.
Manual Surge Point
Allows the Service Technician to manually log the present running
operating conditions into the surge map as a valid surge point.
When this key is pressed, a dialog box appears requesting a special
password to proceed.
Table 118: Navigation
Button
Access level Description
Home
View
Returns user to HOME Screen.
VSD
View
Returns user to VSD Screen.
Surge Map
Service
Causes a jump to the subscreen that displays the surge map.
YK-EP Style B Centrifugal Chiller
118
Summary of Contents for 160.87-OM1
Page 2: ...2 YK EP Style B Centrifugal Chiller ...
Page 6: ...6 YK EP Style B Centrifugal Chiller ...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller ...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228 ...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller ...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230 ...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller ...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232 ...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller ...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234 ...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller ...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236 ...