Motor – High current limit
The Compressor Motor current is greater than or equal to the local or remote Current Limit
Setpoint. The Current Limit Setpoint is programmed over a range of 30 to 100% of the Chiller
Full Load Amps (FLA). When the motor current increases to the Inhibit Open threshold, the Pre-
Rotation Vanes are inhibited from further opening. This prevents a further current rise. If the
current continues to rise to the Start Close threshold, the Vanes begin closing until the current falls
to the Stop Close threshold. Automatic Vane operation is resumed and this message automatically
clears when the motor current decreases to the Allow Open threshold. The thresholds are different
for the various motor starter applications. To allow field calibration of the Solid State Starter (Mod
“A”) Logic Board or CM-2 Current Module, pressing the Pre-Rotation Vanes OPEN key in SERVICE
access level, starts a 10 minute timer during which the current limit thresholds are elevated. Refer
to table:
Table 197: Motor current thresholds
Motor current (%FLA)
Vane control
Electro- mechanical/ Solid State Starter
VSD
Service mode
On rise, inhibit open
100
100
107
On fall, allow open
98
98
106
On rise, start close
104
103
110
On fall, stop close
102
101
109
An example of current limit is as follows: If a Solid Sate Starter chiller FLA is 100 Amps, and the
Current Limit Setpoint is 50%, the following will occur:
•
50 Amps – inhibit vane open
•
52 Amps – vanes begin closing
•
51 Amps – vanes stop closing
•
49 Amps – allow automatic vane control
Load control mode - Access level required: Service
The Compressor Motor Variable Speed Drive has not yet reached full speed after having been
commanded to do so in Manual Speed Control mode. While this is displayed, the Pre-Rotation
Vanes are inhibited from further opening.
Start inhibit messages
Anti-Recycle XX min/Sec
The chiller is inhibited from starting because the 30 minute anti-recycle time has not yet elapsed.
Time remaining is displayed.
Vane Motor Switch Open
The chiller is inhibited from starting because the Pre-Rotation Vanes are not fully closed.
Motor – Current >15% FLA
This start inhibit is instantaneously set whenever the chiller is not running and a motor current
of greater than 15% FLA is detected. The oil pump is started as soon as this fault is detected. The
starting frequency for the Variable Speed Oil Pump is 45.0 Hz. The start inhibit is released when the
motor current decreases to greater than or equal to 15% FLA and the WARNING RESET button is
pressed. A full System Coastdown is performed when this fault is released.
191
YK-EP Style B Centrifugal Chiller
Summary of Contents for 160.87-OM1
Page 2: ...2 YK EP Style B Centrifugal Chiller ...
Page 6: ...6 YK EP Style B Centrifugal Chiller ...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller ...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228 ...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller ...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230 ...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller ...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232 ...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller ...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234 ...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller ...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236 ...