Adaptive Capacity Control (ACC) details screen
Modbus protocol configuration
Figure 42: ACC details screen Modbus protocol configuration
This screen displays detailed information pertaining to the Adaptive Capacity Control (ACC). It is
shown above with the OptiView-to-VSD serial communications hardware/interface in the Modbus
Protocol Configuration. In this configuration, the microboard communicates directly with the VSD
Logic Board using Modbus protocol serial communications. The Microboard performs the ACC
function. The Motor Communications Protocol Setpoint (on the SETUP Screen) is set to Modbus in
this configuration. All Medium Voltage Variable Speed Drives (MVVSD) use Modbus protocol.
Note:
Requires a login access level of SERVICE.
Table 116: Display only
Field/LED name
Description
% Full Load Amps
Displays the motor current as a percentage of chiller Full Load Amps
as calculated by the microboard from current values returned from
the drive Logic Board.
Current Limit Setpoint
Displays the current limit setpoint value in use. This value could
come from a 0 to 20mA, 4 to 20mA, 0 to 10VDC or 2 to 10VDC input
in Analog Remote mode, PWM input in Digital Remote mode, E-Link
or SC-EQ communications interface in ISN Remote mode or locally
programmed value in Local mode.
Motor Run (LED)
Illuminated when the Control Center is commanding the drive to
run. Otherwise, it is extinguished.
Output Frequency
Displays the frequency at which the drive is operating the motor.
This value is returned from the drive Logic Board.
YK-EP Style B Centrifugal Chiller
116
Summary of Contents for 160.87-OM1
Page 2: ...2 YK EP Style B Centrifugal Chiller ...
Page 6: ...6 YK EP Style B Centrifugal Chiller ...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller ...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228 ...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller ...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230 ...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller ...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232 ...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller ...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234 ...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller ...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236 ...