Table 10: Display only fields
Field/LED name
Description
Economizer Discharge
Temperature
Displays the temperature of the refrigerant vapor at the discharge
of the Economizer Compressor before the refrigerant enters the
condenser.
Economizer % Full Load
Amps
Displays the percentage of full load amps (FLA) utilized by the
Economizer Motor.
Economizer Current Limit
Displays the Economizer active motor current limit in percentage at
Full Load Amps.
Economizer PRV Position
Displays how open the PRV vanes are in percentage from 100%
(open) to 0% (closed).
Economizer Pressure
Displays the pressure within the Economizer.
Economizer Saturation
Displays the saturation temperature within the Economizer
calculated from the Economizer Pressure.
Economizer Setpoint
Displays the Level setpoint as set in the Economizer screen.
Economizer Level
Displays the refrigerant level in the Economizer.
Oil Sump Temperature
Displays the temperature of the oil in the sump.
Leaving Condenser Liquid
Temperature
Displays the temperature of the liquid as it leaves the condenser
tube bundle.
Entering Condenser Liquid
Temperature
Displays the temperature of the liquid as it enters the condenser.
Condenser Pressure
Displays the pressure of the refrigerant within the condenser.
Condenser Saturation
Temperature
Displays the saturation temperature of the refrigerant within the
Condenser calculated from the Condenser Pressure.
Condenser Drop Leg
Displays the subcooled temperature at the condenser.
Condenser Level
Displays the refrigerant level within the condenser.
Leaving Chilled Liquid
Temperature
Displays the temperature of the liquid as it leaves the condenser
tube bundle.
Entering Chilled Liquid
Temperature
Displays the entering chilled liquid temperature at the evaporator.
Chilled Liquid Setpoint
Displays the Leaving Chilled Liquid Setpoint which is set either
locally on the Setpoint Screen or remotely from a BAS.
Evaporator Pressure
Displays the evaporator pressure.
Evaporator Saturation
Temperature
Shows the saturation temperature of the Evaporator calculated form
the Evaporator Pressure.
Table 11: Programmable
Button
Access level Description
None
–
–
Table 12: Navigation
Button
Access level Description
Home
View
Returns user to HOME Screen.
System
Service
Returns user to SYSTEM Screen.
29
YK-EP Style B Centrifugal Chiller
Summary of Contents for 160.87-OM1
Page 2: ...2 YK EP Style B Centrifugal Chiller ...
Page 6: ...6 YK EP Style B Centrifugal Chiller ...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller ...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228 ...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller ...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230 ...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller ...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232 ...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller ...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234 ...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller ...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236 ...