Table 89: Programmable
Button
Access level Description
Full Load
Amps
Service
Defines the maximum amps at which the motor can operate. This
value is viewable when logged in at OPERATOR or VIEW access level.
Voltage
Range
Service
Allows the user to select specific line voltage range for voltage
checking. When not disabled, this line voltage range is used to
determine a low line and high line voltage threshold for initiating a
shutdown.
Starting
Current
Service
Defines the maximum allowed motor starting amps. The Solid State
Starter will limit the motor Starting Current to this value.
KWH Reset
Admin
Allows the user to reset the cumulative kilowatt hours.
Open SCR
(Enabled/
Disabled)
Service
Allows the user to enable or disable the Solid State Starter Open
SCR safety detection. This must never be disabled unless under
advisement of the Johnson Controls Factory.
Shorted SCR
(Enabled/
Disabled)
Service
Allows the user to enable or disable the Solid State Starter Shorted
SCR safety detection. This must never be disabled unless authorized
by Johnson Controls.
Table 90: Navigation
Button
Access level Description
Home
View
Returns user to HOME Screen.
Motor Details Service
Moves to a subscreen that provides information and setpoints
pertinent to the Motor Monitoring feature if the Motor Monitoring
option is installed.
Motor Lube
View
Moves to the subscreen allowing operator acknowledgement of the
compressor motor lubrication and viewing of the compressor motor
lubrication parameters.
Economizer
Compressor View
Jumps to the Economizer Compressor screen.
97
YK-EP Style B Centrifugal Chiller
Summary of Contents for 160.87-OM1
Page 2: ...2 YK EP Style B Centrifugal Chiller ...
Page 6: ...6 YK EP Style B Centrifugal Chiller ...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller ...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228 ...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller ...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230 ...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller ...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232 ...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller ...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234 ...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller ...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236 ...