Table 113: Display only
Field/LED
name
Access level Description
Precharge
Relay Output
(LED)
–
Indicates whether the relay controlling the precharge output is
energized.
Trigger SCR
Output (LED)
–
Indicates whether the relay controlling the Trigger SCR Output is
energized.
DC Bus
Voltage
–
Displays the DC Bus voltage as reported by the VSD.
DC Inverter
Link Current
–
Displays the DC Inverter link current as reported by the VSD.
Internal
Ambient
Temperature
–
Displays the ambient temperature inside the VSD cabinet as
reported by the VSD.
Converter
Heatsink
Temperature
–
Displays the heatsink temperature of the converter as reported by
the VSD.
Baseplate
Temperature
–
Displays the baseplate temperature of the 3-phase voltage
regulators as reported by the VSD.
VSD Model
Service
Displays the horsepower configuration of the Variable Speed Drive
control.
100% Full
Load Amps
–
Displays the Full Load Amps value as reported by the VSD.
Table 114: Programmable
Button
Access level Description
Local Motor
Current Limit Operator
Allows the user to specify the maximum allowed motor current (as
a percentage of FLA). When the motor current reaches this value,
the Pre-Rotation Vanes will not be permitted to open further. If the
motor current rises above this value, the Pre-Rotation Vanes will
close to reduce the current to this value.
Pulldown
Demand
Limit
Operator
Allows the user to specify the current limit value (as a percentage
of FLA) to which the chiller will be limited during the specified
pulldown limit time. This value will override the Motor Current
Limit value during this time period. This function is used to provide
energy savings following chiller start-up.
Pulldown
Demand
Time
Operator
Allows the user to set a period of time for which the pulldown
demand limit will be in effect after the chiller starts.
Table 115: Navigation
Button
Access level Description
Home
View
Returns user to HOME Screen.
VSD
View
Returns user to VSD Screen.
115
YK-EP Style B Centrifugal Chiller
Summary of Contents for 160.87-OM1
Page 2: ...2 YK EP Style B Centrifugal Chiller ...
Page 6: ...6 YK EP Style B Centrifugal Chiller ...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller ...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228 ...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller ...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230 ...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller ...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232 ...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller ...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234 ...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller ...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236 ...