Table 138: Programmable
Button
Access level Description
Local Leaving
Chilled Liquid
Temperature
– Setpoint
Operator
This value allows the user to define the Leaving Chilled Liquid
Temperature that is to be maintained by the chiller.
It is programmable over the range of 38.0°F to 72.0°F (water) or
10.0°F to 72.0°F (brine). If Smart Freeze is enabled, the range is
36.0°F to 70.0°F (water). A remote device can provide an analog
signal (0 to 20 mA, 4 to 20mA, 0 to 10VDC or 2 to 10VDC) in Analog
Remote mode, or PWM signal in Digital Remote mode that changes
the setpoint by creating an offset above the operator programmed
BASE Leaving Chilled Liquid Temperature Setpoint. This offset may
be defined from to 10.0°F to 40.0°F above the BASE Setpoint (refer
to the Remote Leaving Chilled Liquid Temperature Setpoint Range
description). Additionally, E-Link or SC-EQ communications (in ISN
Remote mode) can define the setpoint through a serial data stream.
In this case, the incoming setpoint is not an offset that is applied
to the locally programmed BASE Setpoint value, but rather is the
setpoint value itself.
Leaving
Chilled Liquid
Temperature
Cycling
Offset –
Shutdown
Operator
This value allows the user to specify the Leaving Chilled Liquid
Temperature at which the chiller will shut down on a LEAVING
CHILLED LIQUID – LOW TEMPERATURE cycling shutdown. This
is done by defining an offset below the Leaving Chilled Liquid
Temperature Setpoint. It is programmable over a range of 1°F to
70°F below the setpoint, to a minimum cutout of 36°F (water), 34°F
(water with Smart Freeze enabled) or 6°F (brine). It establishes
the minimum allowed temperature for the Leaving Chilled Liquid
Temperature and prevents over-cooling of the building. Anytime
the Leaving Chilled Liquid Temperature Setpoint is increased, the
shutdown threshold is 36.0°F (water) or 6.0°F (brine) for the next
ten (10) minutes. If Smart Freeze is enabled, the threshold is 34.0°F
for the next 10 minutes. After ten (10) minutes have elapsed, the
shutdown threshold becomes the programmed setpoint value.
Leaving
Chilled Liquid
Temperature
Cycling
Offset –
Restart
Operator
This value allows the user to specify the Leaving Chilled Liquid
Temperature at which the chiller will restart after a shutdown on a
LEAVING CHILLED LIQUID – LOW TEMPERATURE cycling shutdown.
This is done by defining an offset above the Leaving Chilled Liquid
Temperature Setpoint. It is programmable over a range of 0°F to
(80 - Local Leaving Chilled Liquid Temp Setpoint). This allows a
maximum restart value of 80°F. The chiller will automatically restart
when this temperature is reached. This setpoint can be used to
reduce chiller cycling by delaying the chiller restart until the cooling
load has increased.
Remote
Analog Input
Range
Operator
This setpoint defines, for the Control Center, the remote signal
range applied for remote reset of the Leaving Chilled Liquid
Temperature Setpoint and Current Limit Setpoint in Analog Remote
mode. If the remote signal is 0 to 10VDC or 0 to 20mA, this setpoint
must be programmed for 0 to 10VDC. If the remote signal is 2 to
10VDC or 4 to 20mA, this setpoint must be programmed for 2 to
10VDC.
YK-EP Style B Centrifugal Chiller
142
Summary of Contents for 160.87-OM1
Page 2: ...2 YK EP Style B Centrifugal Chiller ...
Page 6: ...6 YK EP Style B Centrifugal Chiller ...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller ...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228 ...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller ...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230 ...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller ...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232 ...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller ...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234 ...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller ...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236 ...