Table 71: Display
Field/LED
name
Access level Description
Oil Pump
Drive
Command
Frequency
–
Displays, in Hertz, the frequency being used to power the Oil Pump.
Variable
Speed
Oil Pump
Control
Mode
–
Displays the control mode of the oil pump. It will show the following
messages depending on what the system is doing:
•
Off
•
Pulldown Fixed
•
Pulldown Pre-Lube
•
Pulldown Running
•
Auto
•
Manual
•
Hold
Next Oil Seal
Lubrication
Service
This display will show the time remaining until the next Seal
Lubrication is necessary, when this function is enabled.
Setpoint Oil
Pressure
–
(Variable Speed Oil Pump Only) The Variable Speed Oil Pump (VSOP)
operates to control to a defined Oil Pressure value. During prelube,
and for the first 15 seconds after prelube, this setpoint value is 45.0
PSID. During this time, this field will display the target value. After
15 seconds, this value will display the user-programmed setpoint Oil
Pressure.
Oil Pump
Drive
Command
Frequency
–
(Variable Speed Oil Pump Only) Displays the actual speed command
being sent to the VSOP. This value could be the result of automatic
control based on the Oil Pressure Setpoint, or the result of a manual
speed command.
Manual
Oil Pump
Operation
Time Left
–
Displays the time remaining in the 10-minute Manual Oil Pump
operation described below.
Table 72: Programmable
Button
Access level Description
Raise
Service
This key puts the VSOP control into manual mode and increases the
present speed command by 0.5 Hz to a maximum of 60.0 Hz.
Lower
Service
This key puts the VSOP control into manual mode and decreases the
present speed command by 0.5 Hz to a minimum of 25.0 Hz.
Set
Service
This key allows the user to specify the manual speed which the VSOP
will run between 25 and 60 Hz.
83
YK-EP Style B Centrifugal Chiller
Summary of Contents for 160.87-OM1
Page 2: ...2 YK EP Style B Centrifugal Chiller ...
Page 6: ...6 YK EP Style B Centrifugal Chiller ...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller ...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228 ...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller ...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230 ...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller ...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232 ...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller ...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234 ...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller ...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236 ...