Economizer Solid State Starter screen
Figure 36: Economizer Solid State Starter screen
This screen displays all information pertaining to the Economizer Solid State Starter.
Table 97: Display only
Field/LED name
Description
Motor Run (LED)
Indicates whether the digital output from the controls is
commanding the motor to RUN.
Motor Heater (LED)
Indicates whether the optional Motor Heater is ON or OFF.
Displayed if optional Motor Heater is installed.
Motor Current % Full Load
Amps
Displays the motor current as a percentage of the Full Load Amps
(FLA) value.
Override Threshold Setpoint
Displays the current limit in use. This value could come from a 0 to
20mA, 4 to 20mA, 0 to 10VDC or 2 to 10VDC input in Analog Remote
mode, PWM signal in Digital Remote mode, SC-EQ communication
card in ISN (BAS) Remote mode or a locally programmed value in
Local mode.
Starter Model
Displays the Solid State Starter model that is applied to the chiller.
Starter Models are 7L, 14L, 26L or 33L.
Voltage – Phase A, B, C
Displays the 3-phase input line voltage measured by the Solid State
Starter.
Current – Phase A, B, C
Displays the 3-phase motor current values measured by the Solid
State Starter.
Temperature – Phase A, B, C Displays the temperatures of the Silicon Controlled Rectifier
assemblies.
YK-EP Style B Centrifugal Chiller
102
Summary of Contents for 160.87-OM1
Page 2: ...2 YK EP Style B Centrifugal Chiller ...
Page 6: ...6 YK EP Style B Centrifugal Chiller ...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller ...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228 ...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller ...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230 ...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller ...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232 ...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller ...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234 ...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller ...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236 ...