Economizer capacity control screen
Figure 29: Economizer capacity control screen
This screen displays a view of the economizer capacity control setpoints and buttons. It provides all
necessary inputs for manual control of the economizer.
Table 74: Display only
Field/LED name
Description
Economizing Mode LED
LED lights up when the economizer or the Anti Surge is operating.
Economizer Saturated
Temperature
Displays the saturation temperature within the economizer.
Anti Surge Minimum
Temperature
Displays the minimum temperature that the economizer can go to
before the economizer compressor will start to surge. Efficiency of
the economizer will be the highest at this point.
Delta T
Displays the temperature that is the result of subtracting the
Economizer Saturation Temperature minus the Economizer
Saturation Temperature Setpoint.
Motor Current % FLA
Displays the percent of full load amps of the economizer
compressor motor.
Override Threshold
If Motor Current % full load amps is higher than the Override
Threshold, the capacity control will be overridden, it means the
economizer prerotation vanes can't be opened more to increase the
capacity.
Boost Mode LED
This LED is on whenever the Economizer Operation Mode is Boost or
Boost Anti Surge.
Entering Chilled Liquid
Temperature
Displays the entering chilled liquid temperature at the evaporator
and the condenser.
85
YK-EP Style B Centrifugal Chiller
Summary of Contents for 160.87-OM1
Page 2: ...2 YK EP Style B Centrifugal Chiller ...
Page 6: ...6 YK EP Style B Centrifugal Chiller ...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller ...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228 ...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller ...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230 ...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller ...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232 ...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller ...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234 ...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller ...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236 ...