Table 86: Programmable
Button
Access level Description
Close
–
Pressing this button will set the Condenser Level Control Valve
Mode to Manual, if it had been in Auto and will decrease the current
Condenser Level Control Valve Command by an amount equal to the
Manual Increment, with a minimum limit of 0.0%.
Set
Service
Pressing this button will open a dialog box where the user can
manually enter a valve command. Once a legitimate value has been
entered and the Enter key pressed, the Condenser Level Control
Valve Mode will be set to Manual, if it had been in Auto and the
Condenser Level Control Valve Command will be set to the entered
value.
Auto
Service
This button is only displayed when in Manual Level Control. Pressing
this button returns the control to the PID program.
Change
Setpoints
–
This button is only displayed when signed in at Service Level.
Pressing this button allows the user to select any of the setpoint
parameters using the arrow keys.
Table 87: Navigation
Button
Access level Description
Home
View
Returns user to HOME Screen.
Condenser
Service
Returns the user to the CONDENSER screen.
95
YK-EP Style B Centrifugal Chiller
Summary of Contents for 160.87-OM1
Page 2: ...2 YK EP Style B Centrifugal Chiller ...
Page 6: ...6 YK EP Style B Centrifugal Chiller ...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller ...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228 ...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller ...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230 ...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller ...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232 ...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller ...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234 ...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller ...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236 ...