Display messages
The Status Bar of the display contains a Status Line and, beneath it, a Details Line. The Status Line
contains a message describing the operating state of the chiller; whether it is stopped, running,
starting or shutting down. The Details Line displays Warning, Cycling, Safety, Start Inhibit and other
messages that provide further details of the Status Bar messages. The Status Messages listed
below are displayed on the Status Line. All other messages are displayed on the Details Line.
For messages specific to the Variable Speed Drive, Medium Voltage Variable Speed Drive, Solid
State Starter and Medium Voltage Solid State Starter, refer to the applicable service manual as
follows:
Variable Speed Drive – Service Instructions (Form 160.00-M4)
;
Medium Voltage Variable Speed Drive – Service (Form 160.00-M6)
;
Solid State Starter (Mod “B”) – Operation and Maintenance (Form 160.00-O2)
;
Medium Voltage Solid State Starter – Service (Form 160.00-M5)
.
To aid in the meaning of the message, messages are displayed in different colors as follows:
Table 196: Message colors
MESSAGE
COLOR
Normal Operation
Green
Warning
Yellow
Cycling Shutdown
Orange
Safety Shutdown
Red
Status messages
System ready to start
The chiller is shut down but will start upon receipt of a local or remote start signal.
Cycling shutdown – Auto restart
The chiller is shut down on a cycling shutdown. The cause of the shutdown is still in effect and
is displayed on the Details Line of the Status Bar. The chiller will automatically restart when the
cycling condition clears.
Safety shutdown – Manual restart
The chiller is shut down on a safety shutdown. The cause of the shutdown is still in effect and is
displayed on the Details Line of the Status Bar. The chiller can be started after the safety condition
clears and the Operator presses the WARNING RESET button.
System prelube
A chiller start has been initiated and the pre-start lubrication is being performed. The prelube
duration is either 50 seconds or 180 seconds, as configured with a Microboard Program Switch. The
prelube duration must never be changed by anyone other than a qualified Service Technician. The
standard prelube duration is 50 seconds.
System run
The chiller is running under the condition described in the Details Line of the Status Bar.
189
YK-EP Style B Centrifugal Chiller
Summary of Contents for 160.87-OM1
Page 2: ...2 YK EP Style B Centrifugal Chiller ...
Page 6: ...6 YK EP Style B Centrifugal Chiller ...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller ...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228 ...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller ...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230 ...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller ...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232 ...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller ...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234 ...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller ...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236 ...