Operations screen
Figure 58: Operations screen
This screen allows definition of general parameters having to do with the operation of the chiller.
Table 164: Display only
Field/LED name
Description
Chilller Run Time
Displays the amount of time the chiller has been running since the
last start signal was received. Value is reset to zero when the chiller
enters coastdown. It remains at zero while shutdown and during
System Prelube
Table 165: Programmable
Button
Access level Description
Control
Source
Operator
Defines whether the control of the chiller will be Local, Digital
Remote, Analog Remote, Modem Remote or ISN (BAS) Remote.
Number of
Starts
Admin
Displays the number of the starts the chiller has initiated. This may
be reprogrammed to a desired value (generally when this value has
been reset due to a Microboard replacement) but should not be
done so arbitrarily.
Operating
Hours
Admin
Displays the total accumulated run time of the chiller. This may be
reprogrammed to a desired value (generally when this value has
been reset due to a Microboard replacement), but should not be
done so arbitrarily
Level Control
–
Automatically set to Analog.
OptiSave
–
Automatically set to Disabled.
YK-EP Style B Centrifugal Chiller
164
Summary of Contents for 160.87-OM1
Page 2: ...2 YK EP Style B Centrifugal Chiller ...
Page 6: ...6 YK EP Style B Centrifugal Chiller ...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller ...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228 ...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller ...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230 ...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller ...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232 ...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller ...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234 ...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller ...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236 ...