IM CW140-E
7-18
7.6
Averaging Function
As power in the measured lines may greatly fluctuate, the CW140 is facilitated
with a function to calculate the moving average. The averaging function can
be set to on or off on page 1/2 of the system setting screen or on the last page
of the setup screen in each measurement mode.
Selected number of averaging: 2 to 10 cycles
●
Moving Average Equation
Dn = (Mn – (m – 1) + Mn – (m – 2) + ... + Mn – 1 + Mn) / m
m: Number of averaging cycles to be set
Mn: Measured value at nth measurement
Dn: Moving average at nth measurement (on-screen reading)
m cycles
TIP
• The averaging function cannot be used when in harmonics measure mode because the sampling
method used in this mode is different from other modes.
• For integrated values of electric power and demand, the averaging function does not work even if it is
set to on.
SEE ALSO
For details on the settings, see page 1/2 of the system setting screen, p 5-2, or the last page of the setup
screen in each measurement mode:
Instant mode: p. 8-13
Electric energy mode: p. 9-11
Demand mode: p. 11-12
Summary of Contents for CW140
Page 1: ...User s Manual CW140 CLAMP ON POWER METER IM CW140 E IM CW140 E 3rd Edition July 2001 YK ...
Page 2: ......
Page 14: ......
Page 72: ......
Page 102: ......
Page 138: ......
Page 152: ......
Page 160: ......
Page 200: ......
Page 256: ......
Page 274: ......
Page 276: ......
Page 286: ......
Page 289: ......