11-1
IM CW140-E
Demand Measure Mode
11
Chapter 11 Demand Measure Mode
11.1 About Demand
●
Demand
Demand period:
Defined as the length of time specified to determine
average power.
The CW140 is designed so that you can set a demand
period. (Default of demand period: 30 minutes)
Demand:
An average of power consumed during a demand period.
Maximum demand: The maximum value of a demand that occurs during a
measurement interval.
Example:
Demand period
Start of
demand
End of
demand
Period
Total demand
n
n-1
6
5
4
3
2
1
Current time
TIP
Even if the demand ceases during a demand period, the measured value is not numerically affected at
all since the CW140 calculates average power by dividing it by a time length.
●
Reference Power
You can set a value of reference power between 1 and 1000 kW. (See
Section 11.5, "Setup Data Items of Demand Measure Mode.")
If the demand exceeds the preset reference power, the
mark
appears. The mark disappears each time the CW140 enters a demand
period. This mark appears even after the end of demand if there has been a
case that the demand has exceeded the reference power.