7-1
IM CW140-E
Common Functions of All Modes
7
Chapter 7. Common Functions of All Modes
7.1
Wiring
This section describes how to select and change the type of wiring to
measure and wiring check function. To select and change the type of wiring to
measure, press the
key on the measurement screen.
Refer to Section 3.4, "Diagrams of Basic Wiring." The wiring diagram will be
displayed in the wiring check function.
The following marks will be displayed to show the input terminals of the
voltage probe and current sensing clamp.
Wiring
Voltage (RMS) Input
Current (RMS) Input
1
φ
2W
V1
I1
(CH1)
1
φ
3W
V1
V2
I1
I2
(CH1)
(CH2)
3
φ
3W
V1
V3
I1
I3
(CH1)
(CH3)
3
φ
3W3i
V1
V3
I1
I2
I3
(CH1)
(CH2)
(CH3)
3
φ
4W
V1
V2
V3
I1
I2
I3
(CH1)
(CH2)
(CH3)
2-system load
Wiring
Voltage (RMS) Input
Load
Current (RMS) Input
1
φ
2W
×
2
V1
Load 1
I1-1 (CH1)
Load 2
I1-2 (CH2)
1
φ
3W
×
2
V1
V2
Load 1
I1-1 (CH1), I2-1 (CH2)
Load 2
I1-2 (CH3), I2-2 (CH4)
3
φ
3W
×
2
V1
V3
Load 1
I1-1 (CH1), I3-1 (CH2)
Load 2
I1-2 (CH3), I3-2 (CH4)
TIP
The indications I1 to I3 correspond to the wiring displayed on the screen. The indications CH1 to CH4
correspond to the current input terminals.
Summary of Contents for CW140
Page 1: ...User s Manual CW140 CLAMP ON POWER METER IM CW140 E IM CW140 E 3rd Edition July 2001 YK ...
Page 2: ......
Page 14: ......
Page 72: ......
Page 102: ......
Page 138: ......
Page 152: ......
Page 160: ......
Page 200: ......
Page 256: ......
Page 274: ......
Page 276: ......
Page 286: ......
Page 289: ......