VD300 Series Inverter User Manual
Parameter Description
- 85 -
Chapter 6 Parameter Description
6.1 P00 Basic Function
P00.00
Motor Running Mode
0: V/F control mode
1: Sensor-less vector control mode 0
2: Sensor-less vector control mode 1
0
◎
Select the frequency inverter running mode, in which the V/F control mode can be selected by P04.00
or P21.00 parameter to choose linear V/F, MS V/F, curve V/F or V/F separation control.
V/F control mode:
One unit of inverter can work with several units of motor, no need to install encoder. It is adaptive to
non-high requirement on dynamic response application, as belt conveyor, textile machinery etc.
Vector V/F improve further V/F control performance.
Sensor-less vector control mode 0:
One unit of inverter work with one unit of motor, no need to install encoder. It is adaptive to high
performance requirement application, featured with torque precision high and torque response quick.
Sensor-less vector control mode 1:
One unit of inverter work with one unit of motor, no need to install encoder. It is highly adaptive to
application, especially when motor power is big and controlling performance is better.
P00.01
Running Command
Selection
0: Keypad command channel (L/R OFF)
1: Terminal command channel (L/R ON)
2: Communication command channel
(L/R flashes)
0
○
Select inverter run command source:
Inverter run command include: start, stop, forward, reverse, jogging.
Keypad command channel:
Key” RUN, STOP/RESET” on keypad to realize start, stop, fault reset command.
Terminal command channel:
Through multi-function input terminal to realize forward, reverse, forward jogging, reverse jogging etc.
control command, refer to P05 function code group.
Communication command channel:
Operation command as setup via HOST PC via communication, refer to P15 function code group.
P00.02
Frequency Command
Source A
0
◎
P00.03
Frequency Command
Source B
0: Keypad potentiometer
1: Function code P00.11
2: AI1
3: AI2
4: AI3 (extension card)
5: Simple PLC
6: MS speed operation
7: High speed PULSE input
8: PID control setting
9: Communication setting
4
○
Separately choose A, B group frequency command source (note: A, B channel cannot choose the