VD300 Series Inverter User Manual
Function Parameter Table
- 45 -
P01.03
Braking Current
before Starting
0.0%~100.0%
(inverter rate current)
0.0%
◎
P01.04
Braking Time
before Starting
0.0s~60.0s
0.00s
◎
P01.05
Stop Mode Selection
0: Decelerate to stop
1: Coast stop
0
○
P01.06
Initial Frequency of
Stop Braking
0.00Hz~P00.07 (max output frequency)
0.00Hz
○
P01.07
Waiting Time of Stop
Braking
0.000s: Auto delay
0.001s~60.000s
0.001s
○
P01.08
Stop DC Braking
Current
0.0%~100.0%
0.0%
○
P01.09
Stop DC Braking Time
0.00s~60.00s
0.00s
○
P01.10
Excitation Braking
Coefficient
0: Disabled
100~150: The greater the coefficient, the
greater the braking intensity
0
○
P01.11
Short-circuit Braking
Current
0.0%~150% (100% corresponding
inverter rate current)
0.0%
○
P01.12
Startup Short-circuit
Braking Holding Time
0.00s~60.00s
0.00s
○
P01.13
Stop Short-circuit
Braking Holding Time
0.00s~60.00s
0.00s
○
P01.14
Switchover Mode
between FWD/REV
Rotation
0: Switchover with zero frequency
1: Switchover with over starting frequency
2: Switchover at stop speed reach and
delay
0
◎
P01.15
FWD/REV Rotation
Dead-zone Time
0.0s~3600.0s
0.0S
○
P01.16
Stop Speed
0.00Hz~100.00Hz
0.50Hz
◎
P01.17
Detection Mode of
Stop Speed
0: Detect according to speed set value(no
stop delay)
1: Detect according to speed
feedback(only enabled for vector control)
0
◎
P01.18
Detection Time of
Feedback Speed
0.0s~100.0s (P01.17=1 enabled)
0.50s
◎
P01.19
Delay Time of Stop
Speed
0.0s~100.0s
0.0s
○
P01.20
Running Frequency
Lower than Frequency
Lower Limit Action
0: Running with frequency lower limit
1: Stop
2: Dormant standby
0
◎