VD300 Series Inverter User Manual
Parameter Description
- 133 -
Fig 6.9-1 Diagram of Setting frequency arriving detecting amplitude
P09.10
Frequency Detection
Value 1 (FDT1)
0.00Hz~P00.07 (maximum output
frequency)
50.00Hz
○
P09.11
Frequency Detection 1
Hysteresis
Value
0.0%~100.0% (relative to FDT1)
5.0%
○
P09.12
Frequency Detection
Value 1 (FDT2)
0.00Hz~P00.07 (maximum output
frequency)
50.00Hz
○
P09.13
Frequency Detection 2
Hysteresis
Value
-100.0%~100.0% (relative to FDT2)
5.0%
○
Frequency detection FDT function: when the output frequency exceeds set frequency detection value,
DO indicator signal FDT output is Enabled, until the output frequency drop below detection value and
the difference value exceeding the lagged value, DO indicator signal FDT output is Disabled. On the
max extent to enabled setting 2 FDT detecting points at the same time.
FDT lag amplitude = FDT detection value* FDT lag value.
Fig 6.9-2 FDT signal diagram