VD300 Series Inverter User Manual
Function Parameter Table
- 75 -
1: Hardware current limiting overload
alarm disabled
G type: 160.0%
P13.17
Automatic Current
Limit Level
50.0%~200.0%
P type: 120.0%
◎
P13.18
Frequency Decrease
Rate when Current
Limiting
0.00Hz/s ~50.00Hz/s
10.00Hz/s
◎
P13.19
Phase Loss
Protection
0x00~0x11
Led unit’s digit:
0: Input phase loss protection disabled
1: Input phase loss protection enabled
Led ten’s digit:
0: Output phase loss protection
disabled
1: Output phase loss protection
enabled
Model
Dependent
○
P13.20
Frequency Reduction
Function Selection
when an
Instantaneous Power
Failure
0: Disabled
1: Enabled
0
○
P13.21
Frequency Reduction
Mode Selection when
an Instantaneous
Power Failure
0~1
0
○
P13.22
Frequency Decrease
Rate when an
Instantaneous Power
Failure
(P13.21=0 enabled)
0.00Hz/s~50.00Hz/s
10.00Hz/s
○
P13.23
Deceleration Time
when an
Instantaneous Power
Failure
(P13.21=1 enabled)
0.0s~600.0s
5.0s
○
380VAC corresponding:
420.0VDC
○
P13.24
Estimate Voltage
when an
Instantaneous Power
Failure
200.0VDC~600.0VDC
220VAC corresponding:
240.0VDC
○
P13.25
Short-circuit to
Ground Upon
Power-on
0: Enabled
1: Disabled
0
○
P13.26
Fault Output
Terminals Action
0x00~0x11
Led unit’s digit:
0x00
○