Function Parameter Table
VD300 Series Inverter User Manual
- 76 -
Selection during Fault
0: Action upon under-voltage error
1: No action upon under-voltage error
Led ten’s digit:
0: Action during auto reset
1: No action during auto reset
P13.27
Fault Auto Reset
Times
0~20
0
○
P13.28
Time Interval of Fault
Auto Reset
0.1s~3600.0s
1.0s
○
P13.29
Fan Start Mode
0: Automatic control
1: Fan running all the time
0
○
P13.30
Automatic Frequency
Reduction Selection
when Voltage
Reduction
0: Disabled
1: Enabled
0
○
380VAC corresponding:
513.0VDC
P13.31
Automatic Frequency
Reduction Point when
Voltage Reduction
200.0VDC~600.0VDC
220VAC corresponding:
297.0VDC
○
P13.32
Emergency Stop
Time
0.0s~3600.0s
5.0s
○
Group P14 : Fault Record Parameters Group
Function
Code
Parameter Name
Setting Range
Factory
Default Value
Property
P14.00
Fault Record
Selection
0~3 ( 0: current fault, 1: Last fault, the
bigger the ID, the earlier the fault
occurs)
0
○
P14.01
Fault Code
0: No fault
Er001: Acceleration run over current
(hardware)
Er002: Deceleration run over current
(hardware)
Er003: Constant speed run over current
(hardware)
Er004: Acceleration run over current
(software)
Er005: Deceleration run over
current(software)
Er006: Constant speed run over
current(software)
Er007: Acceleration run overvoltage
Er008: Deceleration run overvoltage
Er009: Constant speed run overvoltage
Er010: Bus under voltage
0
●