VD300 Series Inverter User Manual
Function Parameter Table
- 51 -
P04.06
MS V/F Frequency
Point 3
P04.04~P00.07 (max output frequency)
0.00Hz
○
P04.07
MS V/F Voltage Point
3
0.0%~110.0% (rated motor 1 voltage)
0.0%
○
P04.08
V/F Slip
Compensation Gain of
Motor 1
0.0%~200.0%
0.0%
○
P04.09
V/F Torque Boost
0.0%: Automatic torque boost
0.1%~10.0%
0.0%
○
P04.10
Cutoff Frequency of
Torque Boost
0.0%~50.0% (relative to rated motor 1
frequency)
20.0%
○
P04.11
Low Frequency
Suppression
Oscillation Factor of
Motor 1
0~100
10
○
P04.12
High Frequency
Suppression
Oscillation Factor of
Motor 1
0~100
10
○
P04.13
Suppression
Oscillation Cut-off
Point of Motor 1
0.00Hz~P00.07 (maximum output
frequency)
30.00Hz
○
P04.14
Motor 1 Voltage
Setting Source
Selection
0: Function code P04.15
1: AI1
2: AI2
3: AI3 (extension card)
4: HS pulse input
5: PID control
6: Communication control
0
◎
P04.15
Motor 1 Keypad
Setting Voltage Value
0.0%~100.0%
100.0%
○
P04.16
Motor 1 Voltage
Increasing Time
0.0s~3600.0s
5.0s
○
P04.17
Motor 1 Voltage
Decreasing Time
0.0s~3600.0s
5.0s
○
P04.18
Motor
1
Maximum
Output Voltage
P04.19~100.0% (rated motor 1 voltage)
100.0%
◎
P04.19
Motor 1 Minimum
Output Voltage
0.0%~ P04.18 (rated voltage of the
motor)
0.0%
◎
P04.20
Motor 1 V/F Control
Weak Magnetic
Coefficient
1.00~1.30
1.00
○