VD300 Series Inverter User Manual
Parameter Description
- 135 -
P09.19
Jump Frequency 1
0.00Hz~P00.07 (max output frequency)
0.00Hz
○
P09.20
Jump Frequency
Amplitude 1
0.00Hz~P00.07
(max output frequency)
0.00Hz
○
P09.21
Jump Frequency 2
0.00Hz~P00.07
(max output frequency)
0.00Hz
○
P09.22
Jump Frequency
Amplitude 2
0.00Hz~P00.07
(max output frequency)
0.00Hz
○
P09.23
Jump Frequency
Amplitude 3
0.00Hz~P00.07(max output frequency)
0.00Hz
○
P09.24
Jump Frequency
Amplitude 3
0.00Hz~P00.07(max output frequency)
0.00Hz
○
Swing frequency cycle: the sum of swing amplitude rising time and swing amplitude falling time
Jump frequency is that when target frequency fall within jump frequency range, actual run frequency
will automatically adjust out of the jump frequency range to avoid mechanical resonance frequency
point. As below diagram showed, actual run frequency fall onto the solid line:
Fig6.9-4 Schematic diagram for Jump frequency
P09.27
Set Count Value
P09.28~65535
1000
○
P09.28
Designated Count Value
1~P09.27
500
○
The count value can set counter input DI function. When count value arrive at set counter value,
digital output terminal output signal set by counter and counter stop counting. When the count value
reaches the designated count value, the digital output terminal will output signal of designated
counting value. The counter will continue count till the “setup counting value” is reached. The
designated count value shall not exceed the setup count value.
Counter input DI function recommend using HS DI (HDI) terminal receipt, if input signal frequency is
lower (<500Hz), can also use ordinary DI terminal.
Impulse input
Assign count value
Setting count value
Fig 6.9-5 Diagram of setup counting value and designated counting value