VD300 Series Inverter User Manual
Parameter Description
- 93 -
Fig 6.2-4 Schematic diagram for dead time of FWD/REV rotation
P01.16
Stop Speed
0.00Hz~100.00Hz
0.50Hz
◎
P01.17
Detection Mode of
Stop Speed
0: Detect according to speed set value
(no stop delay)
1: Detect according to speed feedback
(only enabled for vector control)
0
◎
P01.18
Detection Time of
Feedback Speed
0.0s~100.0s (P01.17=1 enabled)
0.50s
◎
P01.19
Delay Time of Stop
Speed
0.0s~100.0s
0.0s
○
When the inverter output frequency decelerate to stop the speed and frequency inverter downtime
(blockade output), motor inertia parking.
When the motor run mode set to vector control, and P01.17 is set to 1, the actual output frequency of
frequency converter is less than P01.16, and detection in the set time of P01.18, frequency inverter
stop; otherwise, the inverter stops at the time that the stop speed running is kept and the time delay is
set by P01.19.
P01.20
Running Frequency
Lower than
Frequency Lower
Limit Action
0: Running with frequency lower limit
1: Stop
2: Dormant standby
0
◎
P01.21
Dormant Recover
Delay Time
0.0s~3600.0s
(corresponding P01.20=2 is effective)
0.0s
О
When the frequency lower limit of frequency inverter set greater than zero, P01.20 is used to set the
frequency inverter run state when inverter real output frequency is lower than the in frequency lower
limit.
When P01.20 set to 2, P01.21 set dormancy recovery delay effectively. If you need to restart the
output again, you must meet the output frequency greater than the frequency lower limit, and more
than the delay time of the cumulative length exceeds the sleep recovery frequency lower limit.
P01.22
Power-on Terminal
Running Protection
Selection
0: Terminal operation command is disabled
when power on
1: Terminal operation command is enabled
when power on
0
О
The terminal run command is disabled:
When the inverter is power on, if the terminal has been effective, after power on, inverter will not
response terminals running commands, run to terminal is disabled after a period of time, frequency
inverter to run normal response to a terminal. In addition, after the inverter failure occurs, terminal