Function Parameter Table
VD300 Series Inverter User Manual
- 62 -
P08.14
PID
Parameter
Switchover Deviation
2
0.0%~100.0%
80.0%
○
P08.15
PID Deviation Limit
0.0%~100.0%
0.0%
○
P08.16
PID Preset Output
Mode
0: Not enable preset output mode
1: Output according to holding time
2: Output when PID feedback<
switchover threshold
3: Output when PID feedback>
switchover threshold
4: Terminal switchover
0
◎
P08.17
PID Preset Output
Value
0.0%~100.0% (As frequency command
relative to max output frequency P00.07)
10.0%
○
P08.18
PID Preset Output
Value Holding Time
0.00s~600.00s
0.50s
○
P08.19
PID
Preset Output
Switchover Threshold
0.0%~100.0% (Relative to PID command
value)
50.0%
○
P08.20
Feedback
Wire-break
Detection Value
0.0%: No detection
0.1%~100.0%
0.0%
○
P08.21
Feedback
Wire-break
Detection Time
0.0s~20.0s
0.0s
○
P08.22
Feedback
Over-limit
Detect Value
0.0%: No detection
0.1%~100.0%
0.0%
○
P08.23
Feedback Over-limit
Detection Time
0.0s~20.0s
0.0s
○
P08.24
PID Dormant
Threshold
P08.25~100.0% (PID feedback range)
100%: Cancel the sleep function
100.0%
○
P08.25
PID Wakeup
Threshold
0.0%~ P08.24 (PID feedback range)
0.0%
○
P08.26
PID Dormant Waiting
Time
0.0s~6000.0s
1.0s
○
P08.27
PID Wakeup Waiting
Time
0.0s~6000.0s
0.5s
○
P08.28
PID Calculation Mode
0: Stop no calculation
1: Stop calculation
0
○
P08.29
PID Output Positive
Max Value
0.0%~100.0%
100.0%
○
P08.30
PID Output Reverse
Max Value
0.0%~100.0%
0.0%
○
P08.31
PID
Feed-forward
Source Selection
0: No feed-forward
1: AI1
0
○