VD300 Series Inverter User Manual
Parameter Description
- 161 -
parameter, you can monitor the communication status.
P15.06
Communication Timeout
Error Handling
0: Alarm and coast to stop
1: No alarm and continue to run
2: No alarm and stop according to the
stop mode(only under the
communication control mode)
3: No alarm and stop according to the
stop mode (under all control mode)
0
○
When set up the communication timeout detection, this parameter is used to set the inverter action
method after communication.
P15.07
Communication
Processing Action
Selection
0x00~0x11
Led unit’s digit:
0: Write with responds
1: Write without responds
Led ten’s digit:
0: Communication encrypting no limit
1: Communication encrypting with limit
0x00
○
The parameter is used to set whether inverter will response data in communication and whether
communication encryption setup is enabled.
Write operation with response: inverter responses data to host PC for read write command.
Write operation with no response: inverter only responses data to host PC read command, no
response data to write command, helpful for improving communication efficiency.
Communication encryption setting is disabled: communication is not limited by user password
encryption.
Communication encryption setting is enabled: communication is limited by user password encryption.
P15.08
Communication to
Modify P00.01 Selection
0: Enable modify
1: Disable modify
1
○
This parameter is used to set up the communication whether to change the run command source.
6.16 P20 Motor 2 Parameter Group
Refer to the detail specification of P02 group motor 1 parameter
6.17 P21 Motor 2 V/F Control Parameter Group
Refer to the detail specification of P04 group motor 1 V/F control parameter group