Function Parameter Table
VD300 Series Inverter User Manual
- 42 -
Chapter 5 Function Parameter Table
The symbols in the function table are described as follows:
○
——It indicates that the parameter setup value can be modified when the inverter is in run state;
◎
——It indicates that the parameter setup value cannot be modified when the inverter is in the run
state;
●
——It indicates that the numerical value of the parameter is the actually measured value, which
cannot be modified;
☆
——It indicates this parameter is “Factory default parameter” and can be set only by the
manufacturer.
P00 Basic Function Parameter Group
Function
Code
Parameter Name
Setting Range
Factory
Default
Value
Property
P00.00
Motor Running Mode
0: V/F control mode
1: Sensor-less vector control mode 0
2: Sensor-less vector control mode 1
0
◎
P00.01
Running Command
Selection
0: Keypad command channel (L/R OFF)
1: Terminal command channel (L/R ON)
2: Communication command channel
(L/R flashes)
0
○
P00.02
Frequency Command
Source A
0
◎
P00.03
Frequency Command
Source B Selection
0: Keypad potentiometer
1: Function code P00.11
2: AI1
3: AI2
4: AI3 (extension card)
5: Simple PLC
6: MS speed operation
7: High speed PULSE input
8: PID control setting
9: Communication setting
4
◎
P00.04
Frequency Command
Superposition
0: K1*frequency command A
1: K2*frequency command B
2: K1*frequency command
A+K2*frequency command B
3: K1*frequency command
A-K2*frequency command B
4: MAX (K1*frequency command A,
K2*frequency command B)
5: MIN (K1*frequency command A,
K2*frequency command B)
Remark: K1: P00.29
K2: P00.30
0
◎