Communication Protocol
VD300 Series Inverter User Manual
- 178 -
0.01H: Forward rotation
0.002H: Reverse rotation
0.003H: Inverter stopping
0.004H: Inverter at fault
0.005H: Inverter at POFF state
Inverter status byte
1
3100H
0.006H: Inverter at Pre-excitation state
R
Special control command byte
Bit
0
1
Bit0
(when
bit1=0)
Motor 1
Motor 2
Bit2
Ready for
running
Ready for
running
Bit3
Motor with
excitation
Motor with
excitation
Inverter status byte
2
3101H
Bit4
Un-overload
pre-alarm
overload
pre-alarm
W
Error code
3102H
Refer to error type description
R
Product code
3103H
R
Output frequency
3200H
0.00Hz~P00.07
R
Set frequency
3201H
0.00Hz~P00.07
R
Motor running
speed
3202H
0RPM~65535RPM
R
BUS voltage
3203H
0.0V~2000.0V
R
Output current
3204H
0.0A~2000.0A
R
Output voltage
3205H
0V~1200V
R
Set torque
3206H
-250.0%~250.0%
R
Output torque
3207H
-250.0%~250.0%
R
Output power
3208H
-300.0%~300.0%
R
Input terminal state
3209H
0x0000~0x003F
R
Output terminal
state
320AH
0x0000~0x000F
R
PID set value
320BH
-100.0%~100.0%
R
PID feedback value
320CH
-100.0%~100.0%
R
AI1 input value
320DH
0.00V~10.00V
R
AI2 input value
320EH
0.00V~10.00V
R
Summary of Contents for VD300 Series