Function Parameter Table
VD300 Series Inverter User Manual
- 74 -
Led ten’s digit:
0: Inverter continues to work after
overload / offload warning
1: Inverter continues to work after offload
alarm and stop to run after overload fault
2: Inverter continues to work after
overload alarm and stop to run after
offload fault
3: Inverter stops after offload / overload
fault
Led hundred’s digit:
0: Detection all the time
1: Detection in the constant speed run
P13.09
Output Over-current
Detection
Value
0.0%: No detection
0.1%~300.0%
0.0%
○
P13.10
Output Over-current
Detection Time
0.0s~100.0s
0.0s
○
P13.11
Output Over-current
Action
0: Terminal output
1: Terminal output, alarm Er016
2: Terminal output, alarm Er016 when
constant speed run
3: Terminal output only in the constant
speed run
0
○
P13.12
Overvoltage Stall
Protective
0: Disabled
1: Enabled
1
○
120%~150%
(standard bus voltage) (380V)
140%
P13.13
Overvoltage Stall
Protective Voltage
120%~150%
(standard bus voltage) (220V)
120%
○
P13.14
Dynamic Braking
Enable
0: Disabled
1: Enabled
1
○
220VAC corresponding:
380.0VDC
P13.15
Dynamic Braking
Voltage
200.0VDC~2000.0VDC
380VAC corresponding:
700.0VDC
○
P13.16
Current Limit
Selection
0x00~0x11
Led unit’s digit: current limiting action
selection
0: Current limiting action disabled
1: Current limiting action enabled
Led ten’s digit: hardware current
limiting overload alarm selection
0: Hardware current limiting overload
alarm enabled
0x01
◎