Function Parameter Table
VD300 Series Inverter User Manual
- 64 -
P09.03
Acceleration Time 1
0.0s~3600.0s
Model
Dependent
○
P09.04
Deceleration Time1
0.0s~3600.0s
Model
Dependent
○
P09.05
Acceleration Time 2
0.0s~3600.0s
Model
Dependent
○
P09.06
Deceleration Time2
0.0s~3600.0s
Model
Dependent
○
P09.07
Acceleration Time 3
0.0s~3600.0s
Model
Dependent
○
P09.08
Deceleration Time 3
0.0s~3600.0s
Model
dependent
○
P09.09
Set Frequency
Reaching Detection
Amplitude
0.00Hz~P00.07 (maximum output
frequency)
0.00Hz
○
P09.10
Frequency Detection
Value 1 (FDT1)
0.00Hz~P00.07 (maximum output
frequency)
50.00Hz
○
P09.11
Frequency Detection
1 Hysteresis
Value
0.0%~100.0% (relative to FDT1)
5.0%
○
P09.12
Frequency Detection
Value 1 (FDT2)
0.00Hz~P00.07 (maximum output
frequency)
50.00Hz
○
P09.13
Frequency Detection
2 Hysteresis
Value
-100.0%~100.0% (relative to FDT2)
5.0%
○
P09.14
Swing Set Mode
0: Relative to the central frequency
1: Relative to the max frequency
(Reserved)
0
●
P09.15
Swing Frequency
Amplitude
0.0%: Close swing frequency function
0.1%~100.0%
0.0%
○
P09.16
Jump Frequency
Amplitude
0.0%~50.0%
0.0%
○
P09.17
Swing
Frequency
Rise Time
0.0s~3000.0s
5.0s
○
P09.18
Swing
Frequency Fall
Time
0.0s~3000.0s
5.0s
○
P09.19
Jump Frequency 1
0.00Hz~P00.07 (max output frequency)
0.00Hz
○
P09.20
Jump Frequency
Amplitude 1
0.00Hz~P00.07
(max output frequency)
0.00Hz
○
P09.21
Jump Frequency 2
0.00Hz~P00.07
(max output frequency)
0.00Hz
○
P09.22
Jump Frequency
Amplitude 2
0.00Hz~P00.07
(max output frequency)
0.00Hz
○