VD300 Series Inverter User Manual
Communication Protocol
- 177 -
0.007H: Reverse jog
0.008H: Jog stop
0.009H: Emergency stop
3001H
Communication set frequency (0~P0.07, Unit:
0.01Hz)
3002H
Torque set value (-3000~3000, 1000
corresponding to 100.0% motor rated current)
3003H
The upper limit torque of motor torque (0~3000,
1000 corresponding to 100% inverter motor
current)
3004H
Braking torque upper limit torque (0~3000, 1000
corresponding to 100% motor rated current)
3005H
The upper limit frequency set value of forward
rotation (0~P00.07, Unit: 0.01Hz)
3006H
The upper limit frequency set value of reverse
rotation (0~P00.07, Unit: 0.01Hz)
3007H
PID setting,
range (0~1000, 1000
corresponding to 100% )
3008H
PID feedback,
range (0~1000, 1000
corresponding to 100% )
Special control command byte
Bit
Value 0
Value 1
Bit0 (when
bit1=0)
Motor 1
Motor 2
Bit2
No action
Torque control
Disabled
Bit3
No action
Pre-excitation
3009H
Bit4
No action
DC braking
300AH
Voltage set value (special for V/F separation use)
(0~1000, 1000 corresponding to 100% motor
rated current)
300BH
Virtual input terminal command, range:
0x000~0x1FF
300CH
Virtual output terminal command, range:
0x000~0x1F
300DH
AO output set value 1 (-1000~1000, 1000
corresponding to 100%)
300EH
AO output set value 2 (-1000~1000, 1000
corresponding to 100%)
Communication set
value address
300FH
PID feed forward value (-1000~1000, 1000
corresponding to 100%)
R/W