25
Any frequency
reached
When the output frequency of inverter into the detection range of
set arbitrary frequency, output ON signal. See the function code
P09.34, P09.35.
26
Any current reached
When the output frequency of inverter into the detection range of
set arbitrary frequency, output ON signal. See the function code
P09.36, P09.37.
27
Current limit
exceeded
The output current of inverter exceed the set current. See the
function code P013.09~P13.11.
28
Communication
virtual terminal
output
The DO output terminals of frequency converter is controlled by
communication. Please refer to the communication protocol.
30
Communication
virtual terminal
output
When the inverter is in a state of downtime and output ON signal
or frequency converter in the run immediately when receives the
stop command output ON signal.
31
Run (non-jog run)
When inverter is in jog running, output ON signal.
32
Length reached
When length counting reach to set length, output ON signal. See
the function code P09.25, P09.26.
33
Braking timing output
The timing output function of inverter. See the function code
P09.57, P09.58.
P06.08
AO1
Analog
Output
Function
0
○
P06.09
AO2
Output
Selection
0
○
P06.10
HDO1
Pulse
Output
Functions
0~25, see table below
0
○
Analog output AO1 and AO2 output range is 0V~10V or 0/4mA~20mA. HDO1 terminal output pulse
frequency range is 0.01kHz~P06.01( the output max frequency of HDO1 pulse output mode), P06.01
can be set from 0.01kHz~100.00kHz.
Pulse or analog signal output 0.0%~100.0% corresponding function as below table:
Set
value
Function
Description
0
Running frequency
100.0% Corresponding the maximum output frequency
1
Set frequency
100.0% Corresponding the maximum output frequency
2
Output current 1
100.0% Corresponding 2 times of rated motor current
3
Output voltage1
100.0% Corresponding 1.5 times of rated inverter voltage
4
Motor rotational speed
100.0% Corresponding 2 times of rated motor speed
5
Output power
100.0% Corresponding 2 times of rated motor power
Summary of Contents for VD300 Series