VD300 Series Inverter User Manual
Parameter Description
- 131 -
P08.39
PID output range (not
including feed forward)
0.0: Unlimited
0.1~150%
100%
○
Set the output range of PID, control PID regulating variable, so control
PID influence on the output.
P08.40
Lower Limit
Frequency
Of Feedback Break Line
Detection
0.00~50.00Hz
10.00
○
When the output frequency is lower than the frequency lower limit, don't detect break line.
P08.41
PID Preset Output
Source Selection
0: Function code P08.17 setting
1: AI1
2: AI2
3: AI3 (Extension card)
4: HS pulse input setting
5: MS speed reference setting
6: Keypad potentiometer setting
0
○
When PID preset output, the selection of the output source determined by the above parameters.