Parameter Description
VD300 Series Inverter User Manual
- 132 -
6.10 P09 Special Function Parameter Group
P09.00
Jog Running Frequency
0.00Hz~P00.07 (max output frequency)
5.00Hz
○
P09.01
Jog Running
Acceleration Time
0.0s~3600.0s
Model
dependent
○
P09.02
Jog Running
Deceleration Time
0.0s~3600.0s
Model
Dependent
○
Target frequency and acceleration / deceleration time when setting jog operation, acceleration /
deceleration time is the time needed when speeding up to P00.16 selected reference frequency.
Note: Start frequency, DC brake and other settings is neglect when jog, accelerate from 0 frequency,
stop run when decelerate to 0 frequency.
P09.03
Acceleration Time 1
0.0s~3600.0s
Model
Dependent
○
P09.04
Deceleration Time1
0.0s~3600.0s
Model
Dependent
○
P09.05
Acceleration Time 2
0.0s~3600.0s
Model
Dependent
○
P09.06
Deceleration Time2
0.0s~3600.0s
Model
Dependent
○
P09.07
Acceleration Time 3
0.0s~3600.0s
Model
Dependent
○
P09.08
Deceleration Time3
0.0s~3600.0s
Model
dependent
○
Acceleration/deceleration time refers to the time needed that frequency from 0.00 Hz
acceleration/deceleration to the reference frequency (P00.16), which is used to set frequency
changing slope. There Provide 4 groups of acceleration/deceleration time to selection, through digital
input terminal to choose parameters (refer to P05 parameter group). If there is no terminal input
option to acceleration/deceleration, then terminal selection is disabled, so acceleration/deceleration
time is group 0 accordingly.
P09.09
Set Frequency Reaching
Detection Amplitude
0.00Hz~P00.07 (maximum output
frequency)
0.00Hz
○
When the output frequency is within positive/negative detecting range of preset frequency, DO output
terminal output ON signal (the DO terminal has to set “set frequency arrival function). As below
diagram (take MS speed set frequency to illustrate):