Operation and Maintenance Manual (DTR) iSWAY
®
Set of products
Version 1.8 of 2.2021
67
Fig. 13.9. Block diagram for the connection of the TSS-1-24VDC Control and Display Panel to the iSWAY-FC ( TSS-X-
24VDC supply with iSway is optional) with double air intake system (optional)
Key:
- Control and Display Panel
- Static measurement of pressure difference
Ø5 impulse
cables
- Damper
- BLE24
–
BELIMO actuator
Rescue crews access point
(monitoring room)
Double air intake system
WIRING
Designation on
the diagram
Automation elements connections
Cable type
A1
Guaranteed power supply cable
3x400V for iSWAY-FC/-WFC/-RFC
NHXH FE180/PH90 5x cross section
C1
Control-power supply cable
24 VDC (double intake)
HDGs FE180/PH90 3x1,5
C8
Guaranteed power supply cable
TSS-X-24 VDC
HDGs FE180/PH90 3x2,5
D2
Global FirsBus bus loop
HTKSH FE180/PH90 ekw 2x2x0,8
E2
Cables:
ALARM SAP (NC)
Operation confirmation (NO)
Collective failure (NC)
HTKSH FE180/PH90 3x2x0,8