NOTE!
In the event of a temperature sensor malfunction, the "Collective failure" light on the TSS or TS
panel and the MAC-FC controller issues a fault signal to the CSP. If a sensor malfunction is
detected, inform the SMAY service immediately. Do not repair or replace the sensor yourself.
This can only be done by SMAY service or an authorised SMAY service.
15.3.
MAC-D-Min controller (2 and 4)
The MAC-D-Min is a digital pressure controller, designed to control 1 to 2 (2) and 3 to 4 (4)
damper actuators. It is equipped with an internal pressure sensor and connectors for power and
transmission via two Local FireBUS® channels. The built
-in internal microprocessor system
performs linearity corrections taking into account, among other things, the operating temperature
and the characteristics introduced during calibration. The high accuracy and stability of the
measurement is ensured by the use of high-end calibration devices and a long ageing process of
the device components.
The MAC-D-Min controller should be connected to the PZ box with a specified wire (or wires) of
maximum 20 m length.
Fig.15.7 MAC-D Min controller (2 on the left, 4 on the right) - inside view.
24VDC power supply.
IP54 protection class is delivered as standard. On request IP65 class can be delivered.
For details and technical information, see DTR MAC-D Min.
Connection and wiring diagrams can be found in section 13.
1.
Cover of electronics
2.
LED diode: green (power supply confirmation)
3.
LED diode: yellow, green, red
4.
Zeroing button
5.
USB service socket
6.
Pressure stub pipes
7.
Earthing assembly
8.
Diaphragm ventilator
9.
USB transmission signalization
10.
Cover of electronics
11.
LED diode: green (power supply confirmation)
12.
LED diode: yellow, green, red
13.
Zeroing button
14.
USB service socket
15.
Pressure stub pipes
16.
Earthing assembly
17.
Diaphragm ventilator
18.
USB transmission signalization