background image

Operating instructions

A2D250-AI14-10

Translation of the original operating instructions

ebm-papst Mulfingen GmbH & Co. KG

Bachmühle 2
D-74673 Mulfingen
Phone +49 (0) 7938 81-0
Fax +49 (0) 7938 81-110
[email protected]
www.ebmpapst.com

CONTENTS

1. SAFETY REGULATIONS AND NOTES

1

1. SAFETY REGULATIONS AND NOTES

Please read these operating instructions carefully before starting to work
with the device. Observe the following warnings to prevent malfunctions
or physical damage to both property and people.
These operating instructions are to be regarded as part of this device.
If the device is sold or transferred, the operating instructions must
accompany it.
These operating instructions may be duplicated and forwarded for
information about potential dangers and their prevention.

1.1 Levels of hazard warnings

1

1.1 Levels of hazard warnings

These operating instructions use the following hazard levels to indicate
potentially hazardous situations and important safety regulations:

DANGER

Indicates an imminently hazardous situation which, if not
avoided, will result in death or serious injury. Compliance with
the measures is mandatory.

WARNING

Indicates a potentially hazardous situation which, if not avoided,
could result in death or serious injury. Exercise extreme
caution while working.

CAUTION

Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury or damage of property.

NOTE

A potentially harmful situation can occur and, if not avoided, can
lead to property damage.

1.2 Staff qualification

1

1.2 Staff qualification

The device may only be transported, unpacked, installed, operated,
maintained and otherwise used by qualified, trained and authorised
technical staff.
Only authorised specialists are permitted to install the device, to carry
out a test run and to perform work on the electrical installation.

1.3 Basic safety rules

1

1.3 Basic safety rules

Any safety hazards stemming from the device must be re-evaluated
once it is installed in the end device.
Observe the following when working on the unit:

;

Do not make any modifications, additions or conversions to the
device without the approval of ebm-papst.

1.4 Electrical voltage

1

1.4 Electrical voltage

;

Check the electrical equipment of the device at regular intervals, refer
to chapter 5.2 Safety test.

;

Replace loose connections and defective cables immediately.

DANGER
Electrical load on the device

Risk of electric shock
→ Stand on a rubber mat if you are working on an electrically

charged device.

WARNING
Terminals and connections have voltage even with a
unit that is shut off

Electric shock
→ Wait five minutes after disconnecting the voltage at all poles

before opening the device.

2

1.5 Safety and protective functions

2

1.6 Mechanical movement

2

1.7 Emission

2

1.8 Hot surface

2

1.9 Transport

2

1.10 Storage

2

1.11 Disposal

3

2. PROPER USE

4

3. TECHNICAL DATA

4

3.1 Product drawing

5

3.2 Nominal data

5

3.3 Technical features

6

3.4 Mounting data

6

3.5 Transport and storage conditions

6

4. CONNECTION AND START-UP

6

4.1 Connecting the mechanical system

6

4.2 Connecting the electrical system

7

4.3 Connection of the cables

8

4.4 Connection screen

9

4.5 Checking the connections

9

4.6 Switch on device

9

4.7 Switching off the device

9

5. MAINTENANCE, MALFUNCTIONS, POSSIBLE

CAUSES AND REMEDIES

10

5.1 Cleaning

10

5.2 Safety test

Item no. 12218-5-9970 · Revision 76115 · Release 2012-03-06 · Page 1 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for A2D250-AI14-10

Page 1: ...ied trained and authorised technical staff Only authorised specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety r...

Page 2: ...wellery could become entangled and pulled into the device You could be injured Do not wear any loose clothing or jewellery while working on rotating parts Protect long hair by wearing a cap 1 7 Emissi...

Page 3: ...tions Improper use Using the device in the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Moving air that c...

Page 4: ...sures have the unit mm 1 Direction of air flow A 2 Depth of screw max 5 mm 3 Connection line PFA 4G 4x brass lead tips crimped Item no 12218 5 9970 Revision 76115 Release 2012 03 06 Page 4 10 ebm paps...

Page 5: ...ge VAC 480 Connection Y Frequency Hz 60 Type of data definition fa Valid for approval standard CE Speed min 1 2680 Power input W 170 Current draw A 0 23 Max back pressure Pa 110 Min ambient temperatur...

Page 6: ...s that meet the specified installation requirements for voltage current insulation material load etc Route cables such that they cannot be touched by any rotating parts CAUTION Electrical voltage The...

Page 7: ...requency converter only after consultation with ebm papst Fit sinusoidal filters that work on all poles live live and live earth between the frequency inverter and the motor for operation with frequen...

Page 8: ...ion of rotation by reversing two phases Three phase motor Y Star connection L1 black L2 blue L3 brown PE green yellow Item no 12218 5 9970 Revision 76115 Release 2012 03 06 Page 8 10 ebm papst Mulfing...

Page 9: ...ltage even with a unit that is shut off Electric shock Wait five minutes after disconnecting the voltage at all poles before opening the device CAUTION The motor restarts automatically when operating...

Page 10: ...eplacement of the device Check the device for damage to blades and housing Visual inspection At least every 6 months Replacement of the device Mounting the connection lines Visual inspection At least...