Operation and Maintenance Manual (DTR) iSWAY
®
Set of products
Version 1.8 of 2.2021
60
resistors must be installed on the contact side of the CSP Control and Monitoring Module
according to the instructions in Figure 13.14. The iSWAY-FC
®
, iSWAY-WFC
®
, iSWAY-RFC
®
transmit a confirmation and a collective fault signal to the CSP.
Fig. 13.4. Connection diagram of MAC-FC controller (devices in SzA-FCP/SzA-FCK) to SAP system
13.2.
Electrical parameters
Table 13.2. Electrical data sheet for iSWAY-
FC®
Type
Supply
voltage
Active
power
Apparent
power
Protection
on the device
Suggested
protection
in the main
switchboard
Suggested power cables
for the device
[VAC]
[kW]
[kVA]
Type
[A]
Type
0.3
3x400
3.38
3.45
B 10A
gG 16A
NHXH FE180/PH90 5x2,5
1
0.12
3x400
5.47
5.57
B 16A
gG 20A
NHXH FE180/PH90 5x4
1
1.17
3x400
5.26
5.36
B 16A
gG 20A
NHXH FE180/PH90 5x4
1
1.20
3x400
6.96
7.10
B 16A
gG 20A
NHXH FE180/PH90 5x4
1
1.24
3x400
9.22
9.40
B 20A
gG 25A
NHXH FE180/PH90 5x6
1
2.31
3x400
9.22
9.40
B 20A
gG 25A
NHXH FE180/PH90 5x6
1
2.39
3x400
13.00
13.26
B 32A
gG 40A
NHXH FE180/PH90 5x10
1
2.47
3x400
17.40
17.75
B 40A
gG 50A
NHXH FE180/PH90 5x16
1
2.75
3x400
21.26
21.34
B 50A
gG 63A
NHXH FE180/PH90 5x16
1
Table 13.3. Electrical data sheet for iSWAY-
WFC®
Type
Supply
voltage
Active
power
Apparent
power
Protection
on the device
Suggested
protection
in the main
switchboard
Suggested power cables
for the device
[VAC]
[kW]
[kVA]
Type
[A]
Type
1.1
3x400
2.02
2.06
B 6A
gG 10A
NHXH FE180/PH90 5x2,5
1
1.5
3x400
2.50
2.54
B 6A
gG 16A
NHXH FE180/PH90 5x2,5
1
2.2
3x400
3.20
3.26
B 10A
gG 16A
NHXH FE180/PH90 5x2,5
1
1
The maximum cable length of 70m with 20% share of the hot zone was assumed - voltage drop not
exceeding 3%. For other conditions, the cross-section must be recalibrated
CABLE DESCRIPTION
DESIGNATION
CABLE SORT
CABLE TYPE
E2
HTKSH FE180/PH90
3x2x0,8
SIGNAL DESCRIPTION FOR SAP:
1
–
FIRE SIGNAL FROM SAP (NC)
2
–
DEVICE OPERATION CONFIRMATION
“CORRECT OPERATION”
FOR SAP (NO)
3
–
COLLECTIVE FAILURE OF THE DEVICE FOR SAP (NC)