Operation and Maintenance Manual (DTR) iSWAY
®
Set of products
Version 1.8 of 2.2021
61
3.0
3x400
4.14
4.22
B 10A
gG 16A
NHXH FE180/PH90 5x4
1
5.5
3x400
7.09
7.23
B 16A
gG 20A
NHXH FE180/PH90 5x4
1
Table 13.4. Electrical data sheet for iSWAY-
RFC®
Type
Supply
voltage
Active
power
Apparent
power
Protection
on the device
Suggested
protection
in the main
switchboard
Suggested power cables
for the device
[VAC]
[kW]
[kVA]
Type
[A]
Type
1.5
3x400
2.52
2.57
B 6A
gG 10A
NHXH FE180/PH90 5x2,5
1
2.2
3x400
3.34
3.40
B 10A
gG 16A
NHXH FE180/PH90 5x2,5
1
3.0
3x400
4.11
4.19
B 10A
gG 16A
NHXH FE180/PH90 5x2,5
1
4.0
3x400
5.25
5.36
B 16A
gG 20A
NHXH FE180/PH90 5x4
1
5.5
3x400
6.93
7.07
B 16A
gG 20A
NHXH FE180/PH90 5x4
1
7.5
3x400
9.19
9.37
B 20A
gG 25A
NHXH FE180/PH90 5x6
1
Table 13.5. Summary of electrical parameters of TSS-1...3, TS-X and MSPU
Type
Supply
voltage
Active
power
Apparent
power
Protection
on the device
Suggested
protection
in the main
switchboard
Suggested power cables
for the device
[VAC]
[W]
[VA]
Type
[A]
Type
TSS-1
1x230
16
20
1.25 delayed
B6
NHXH FE180/PH90 3x1,5
2
TSS-2
1x230
16
20
1.25 delayed
B6
NHXH FE180/PH90 3x1,5
2
TSS-3
1x230
16
20
1.25 delayed
B6
NHXH FE180/PH90 3x1,5
2
TS-X
TS-X/YR
1x230
16
20
1.25 delayed
B6
NHXH FE180/PH90 3x1,5
2
Power
supply to
MSPU
1x230
18
22
-
B6
socket
Table 13.6. Electric parameters of the TSS-1...3-24V, MAC-D-MIN, P-MAC and T-MAC device
UrządzenieTSS
-X-24V, MAC-D MIN, P-MACF, T-MACF
Type
Supply
voltage
Active power
Suggested power cables for the device
[VDC]
[W]
Type
TSS-1-24V
24
6
HDGs FE180/PH90 3x2,5
TSS-2-24V
24
11.5
HDGs FE180/PH90 3x2,5
TSS-3-24V
24
14.5
HDGs FE180/PH90 3x2,5
MAC-D MIN
24
12
HDGs FE180/PH90 3x1,0
P-MACF
24
2.2
HDGs FE180/PH90 3x1,0
T-MACF
24
1.2
Powered by Local FireBus
2
it is assumed that the length of the supply cables does not exceed 60m with 20% share of the hot zone
and acceptable voltage drops of 5%. For other conditions, the cross-section must be recalibrated