Operation and Maintenance Manual (DTR) iSWAY
®
Set of products
Version 1.8 of 2.2021
64
Fig. 13.6. Block diagram for the connection of the TSS-1 Control and Display Panel to the iSWAY-WFC device
Key:
- Control and Display Panel
- Static measurement of pressure difference
Ø5 impulse cables
- Damper
- BLE24
–
BELIMO actuator
Rescue crews access point
(monitoring room)
WIRING
Designation on
the diagram
Automation elements connections
Cable type
A1
Guaranteed power supply cable
3x400V for iSWAY-FC/-WFC/-RFC
NHXH FE180/PH90 5x cross section
A2
Ventilator power supply
3x400V for iSWAY-FC/-WFC/-RFC
NHXCH FE180/PH90 4x cross section
B1
Guaranteed power supply 1x230VAC
MSPU, TS, TSS
NHXH FE180/PH90 3x1,5
C1
Control-power supply cable
24 VDC (double intake)
HDGs FE180/PH90 3x1,5
D2
Global FireBus bus loop
HTKSH FE180/PH90 ekw 2x2x0,8
E2
Cables:
ALARM SAP (NC)
Operation confirmation (NO)
Collective failure (NC)
HTKSH FE180/PH90 3x2x0,8
F1
Control/power supply cable
24 VDC (shut-off damper)
HTKSH FE180/PH90 2x2x1,0
G1
Power supply, alarm, failure, smoke detector
signal cable,
HTKSH FE180/PH90 3x2x0,8