15.8.
TS control panel
The control panel (TS) is always mounted on the object together with the MSPU. There is a
light on the panel to confirm the power supply to the panel. This panel must be installed at the
emergency services access point. On the TS panel there is a common attachment "Manual fan
activation", which activates all devices. Because each device can be individually stopped from the
TS panel - it is possible to switch on a single or any group of devices. For each device there is a
switch "SAP fire cancelling", which makes it possible to stop the device. ISWAY® units work
autonomously and require a stop after receiving a fire signal. With this switch we can also stop the
device, making it impossible for it to work. For security reasons, this switch has a key lock. There
is a "Smoke Detector Lock" switch or a "Double Intake Switch" switch for each device. This switch
has two interchangeable functions, depending on whether the device has a double intake system.
If there is a double air intake after the appearance of smoke in the air handling unit, it
automatically switches to the second air source and the switch allows to return to the original
source. In the absence of a double inlet, the appearance of smoke in the duct stops the unit. The
switch then allows you to ignore the information about the smoke and causes the device to work.
Confirmation of smoke occurrence in the channel is displayed on the MSPU panel located near
the TS.
Table 15.6. Basic dimensions of the TS panel.
No.
TS Dimensions
Installation
Overall
SxW [mm]
SxWxG [mm]
TS-4; TS-6
260x320
313x340x188
TS-7; TS-16
556x449
605x522x263
TS-17; TS-32
556x649
605x722x263
TS-33, TS-36
756x849
805x922x313
Power supply: 230VAC.
Protection class: IP65.