NOTE:
"Separate overcurrent (short-circuit) protection is required for each of the power outlets. The
requirement applies to each power circuit, both 24VDC and 230VAC and 3x400VAC. Overcurrent
protections must be installed directly behind the power distribution point, the selectivity of the
protections used must be ensured”
13.3.
Wiring block diagrams
The iSWAY-FC
®
, iSWAY-WFC
®
, iSWAY-RFC
®
units are combined as standard with a Control
and Display Panel (TSS-X, TSS-X-24V) or with the Control Panel and Devices Operation Status
Monitoring (TS-..., MSPU), with a double intake system, with P-MACF pressure sensors, MAC-D
Min controllers, Fire Alarm System (SAP), making up the SAFETY WAY
®
system.
The diagrams below show typical solutions for securing areas such as: staircases, lift shafts and
vestibules. The last diagram of Figure 13.12 in this point shows an example of the connection
diagram of an extended Safety Way
®
system.
Detailed wiring diagrams of the individual system components can be found in the next chapter.