Operation and Maintenance Manual (DTR) iSWAY
®
Set of products
Version 1.8 of 2.2021
103
3.0
VLT FC102 IP20
3x400/3,0
5.5
VLT FC102 IP20
3x400/5,5
On request, IP66 inverter can be delivered
Table 14.8. Series of frequency inverters used in iSWAY-
RFC®.
Type of device
Type
Power
supply[VAC]/Power[kW]
iSWAY-
RFC ®
1.5
VLT FC102 IP20
3x400/1,1
2.2
VLT FC102 IP20
3x400/1,5
3.0
VLT FC102 IP20
3x400/2,2
4.0
VLT FC102 IP20
3x400/3,0
5.5
VLT FC102 IP20
3x400/5,5
7.5
VLT FC102 IP20
3x400/7,5
On request, IP66 inverter can be delivered
NOTE!
If the inverter is not powered (the green "ON" light on the inverter is not lit), first check whether
the main switch is in position "0". If the main switch is in position "1", it may mean that one of
the fuses has tripped: 1F1, 1F2, 1F3, in the automation cabinet.
In the event of a frequency inverter malfunction, the "Collective fault" light on the TSS or TS
panel
, or “Alarm” light on the inverter and the MAC
-FC controller issues a fault signal to the
CSP. If a inverter malfunction is detected, inform the SMAY service immediately. Do not repair
or replace the frequency inverter or change its parameter settings yourself. This can only be
done by SMAY service or an authorised SMAY service.
14.8.
ZSPM-150-10 Power Supply
ZSPM-150-10 power supply is installed inside SzA-FCK and SzA-FCP automation
cabinets.
Provides 24 VDC power supply with battery backup.
Rys.14.13. ZSPM power supply
Tabela 14.9. ZSPM-150-10 technical parameters.
Rated output voltage (25°C)
27,1V
Working temperature
-25
…
+55
°
C
Functional class PN-EN 12101-10
A
Protection class PN-EN 60950-1 + A1
I