special care must be taken to ensure that they are not bent or clamped by other elements. The
connection points of the pressure measurement lines are located on the housing of the device
from the operating side. It is recommended that the pressure measuring point be routed to a
sheltered location to eliminate the adverse effects of air blasts.
The pressure (compressor) measurement inside the ventilation duct for the iSWAY-FC (similarly
to the iSWAY-RFC) is shown in figure 11.22. The measuring points should be located on three
different walls, on a straight section of the ventilation duct behind the silencer. Pneumatic pipes
are terminated at the measurement points with stubs inserted into the ventilation duct.
Fig. 11.22. Compression measurement point in the ventilation duct.
Fig. 11.23. Static pressure measurement point (wall-mounted version).
Ø
6 mm impulse tube
in a
Ø
18 mm corrugated pipe
Ø
6 mm impulse tube
in a
Ø
18 mm corrugated pipe
SCAME 100x100 type box
Pressure measuring points