Fig. 14.10. View of SzA-FCP Automatic Control Cabinet.
Table 14.4. Series of SzA-FCP Automatic Control Cabinet.
SzA-FCP
0.3
0.12
1.17
1.20
1.24
2.31
2.39
2.47
2.75
Inverter
power [kW]
2.2
4.0
4.0
5.5
7.5
7.5
11.0
15.0
18.5
Overcurrent
protection of
the inverter
B10
B16
B16
B16
B20
B20
B32
B40
B50
NOTE!
The absence of the indication "POWER CONTROL" first means that the main switch is in the "0"
position. If the main switch is in position "1", it may mean that one of the fuses has tripped: 1F1,
1F2, 1F3, 1F5, 1F6 in the SzA-FCP cabinet or there is a damage to the power supply circuit of a
frequency inverter (SzA-FCP cabinet - inverter).
Description of security features: SzA-FCP
1. 1F1, 1F2, 1F3 - frequency inverter protection (3x400V) - Tables (13.2, 14.4)
2. 1F4 - Anti-Frost protection (1x230V) - B10
3. 1F5 - power supply protection (1x230V) - C10
4. 1F6 - protection of 24VDC circuits in the cabinet (1x24V) - 3.15A
5. 1F7 - MAC-FC controller protection (1x24V) - 3.15A
6. 1F8 - 24VDC power output protection for peripheral devices (1x24V) - 3.15A
7. 1F9 - 24VDC power output protection for TSS-X-24V panel (1x24V) - 3.15A
NOTE!
In the event of a SzA-FCP cabinet malfunction (or power supply loss), the "Collective fault" light
on the TSS or TS panel and the MAC-FC controller issues a fault signal to the CSP.
If a SzA-FCP cabinet malfunction is detected, inform the SMAY service immediately. Do not
repair or replace the cabinet yourself. This can only be done by SMAY service or an authorised
SMAY service.